SAFEBOX LPS II 230-200

Safety power supply system with power limitation (LPS system, Low Safety Power Supply System) DIN EN 50171

Central power supply system with 4 or 8 final circuits, in changeover mode with limitation of the output power to 200 W / 1 h, 200 W / 3 h or 70 W / 8 h. The LPS II is idesigned to supply the safety lighting DIN EN 50172 (VDE 0108-100) in case of failure of the general power supply.

The VRLA battery has a life expectancy of 12 years plus (long-life).

Operation and display of the test results are carried out via a multi-touch display. Commissioning takes place automatically after activation. Circuit types of the circuits and operating modes of the emergency luminaires can bee freely parameterisable.

The LPS II has a web server with a network connection that can be accessed via a web browser. Up to 200 building plans can be stored in the web server, on which the mounting locations of the emergency luminaires and their operating status can be displayed.

Performance

 

  • Max. output 200 W / 1 h, 200 W / 3 h or 70 W / 8 h
  • 4 or 8 final circuits (1.0 A) with circuit and individual luminaire monitoring
  • Luminaires freely programmable via the LPS II and / or the luminaire module in BS / DS (only with optional ELC address module)
  • 5“ multi-touch-capable colour display including a USB port for connecting external storage, a USB printer, a keyboard or a mouse
  • Automatic commissioning
  • 4 non-floating 230 V inputs for querying light switch positions (freely programmable)
  • 4 floating control inputs (freely programmable)
  • 4 relay outputs for messages (freely programmable)
  • 1 connection for MFT4 status and control panel
  • 1 connection as monitored current loop for external phase monitor
  • 1 contact for safety light blocking during idle times
  • 24 groups freely programmable
  • 24 timer freely programmable
  • Function of direction-variable luminaires (RIVA / only with ELC address module)
  • RJ-45 TCP-IP network connection
  • Integrated web server with visualization of the mounting locations of the safety luminaires
  • Web visualization of up to 125 LPS II devices

Technical specifications

 

Power supply 1/N/PE AC 50Hz 230V
External back-up fuse 16A
System voltage 24V/230V AC/DC
Output terminals 1.5mm² to 2.5mm²
Housing Steel plate RAL7016
Ambient temperature 5°C to 30°C
Cable entry from the top and the back

 

Dimensions 454 x 675 x 172 mm
Weight not including batteries 17.6 kg

 

Protection class IP20
Safety class I