SAFEBOX II 230-200-S
Safety power supply system with power limitation (LPS system, low power safety supply system) - EN 50171
Central safety power supply system with 4 or 8 final circuits, in changeover mode with limitation of the output power to 200 W / 0.5h, 200 W / 1h, 200 W / 3h or 70 W / 8h. The LPS II is designed to supply the safety lighting EN 50172 in case of failure of the general power supply.
The VRLA battery has a life expectancy of 10 years (long-life).
Operation and display of the test results are carried out via a multi-touch display. Commissioning takes place automatically after activation. Circuit types of the circuits and operating modes of the emergency luminaires can be freely adjusted.
The LPS II has a web server with a network connection that can be accessed via a web browser. Building plans can be stored in the web server, on which the mounting locations of the emergency luminaires and their operating status can be displayed.
Preferences
- Max. output 200 W / 0.5h, 200 W / 1h, 200 W / 3h or 70 W / 8h
- 4 or 8 final circuits (1.0 A) with circuit and individual luminaire monitoring
- Luminaires freely programmable via the LPS II and / or the luminaire module in NMM / MM (only with optional ELC address module)
- 5“ multi-touch-capable colour display including an USB port for connecting external storage, a USB printer, a keyboard or a mouse
- Automatic commissioning
- 4 non-floating 230 V inputs for querying light switch positions (freely programmable)
- 4 floating control inputs (freely programmable)
- 4 relay outputs for messages (freely programmable)
- 1 connection for MFT4 status and control panel
- 1 connection as monitored safety loop for external phase monitor
- 1 contact for safety light blocking during idle times
- 1 bus connection (RS485) for external bus components (mimic panel, mains monitor, I/O box)
- 24 groups freely programmable
- 24 timer freely programmable
- Function of direction-variable luminaires (RIVA / only with ELC address module)
- Possibility of switching off individual circuits during battery operation (time adjustable)
- Reduction of luminous flux to 20% for individual circuits (only with ELC-LR address module)
- RJ-45 network connection including Modbus TCP protocol
- Integrated web server with visualization of the mounting locations of the safety luminaires
- Web visualization of up to 125 LPS II devices
Technical specifications
| Voltage supply | 1/N/PE AC 50 Hz 230V |
| External back-up fuse | 16A |
| System voltage | 24 V / 230V AC / DC |
| Output terminals | 1.5 mm² to 2.5 mm² |
| Material | Sheet steel |
| Colour | anthracite grey |
| Ambient temperature | 5°C to +30°C |
| Cable entry | from the top and the back |
| Dimensions (W x H x D) | 454 x 675 x 172 mm |
| Weight without batteries | 17.60 kg |
| Protection class | IP20 |
| Safety class | I |